LL 141
- Home
- LL 141
SECTION BC 1024 LUMINOUSEGRESS PATH MARKINGS
- 1. Luminous egress path markings shall not be required on the level of exit discharge in lobbies that serve as part of the exit path in accordance with Section 1027.1, Exception 1.
- 2. Luminous egress path markings shall not be required in areas of open parking garages that serve as part of the exit path in accordance with Section 1027.1, Exception 3.
1024.2 Required markings. Egress path markings shall be provided in exit enclosures, including vertical exit enclosures, horizontal exits, and exit passageways, in accordance with Sections 1024.2.1 through 1024.2.9. Entrances to exit enclosures shall be provided with exit signs in compliance with Section 1024.2.6.1.
1024.2.1 Steps. A solid and continuous stripe shall be applied to the horizontal leading edge of each step and shall extend for the full length of the step. Outlining stripes shall have a minimum horizontal width of 1 inch (25 mm) and a maximum width of 2 inches (51 mm). The leading edge of the stripe shall be placed at a maximum of ½ inch (13 mm) from the leading edge of the step and the stripe shall overlap the leading edge of the step by not more than ½ inch (13 mm) down the vertical face of the step. Outlining stripes on steps shall comply with Figure S101.1(2) of Appendix S.
1024.2.2 Landings. The leading edge of landings shall be marked with a stripe consistent with the dimensional requirements for steps. Stripes on landings shall comply with Figure S101.1(3) of Appendix S.
1024.2.3 Handrails. All handrails and handrail extensions shall be marked with a solid and continuous stripe having a minimum width of 1 inch (25 mm). The stripe shall be placed on the top surface of the handrail for the entire length of the handrail, including extensions and newel post caps. Where handrails or handrail extensions bend or turn corners, the stripe shall not have a gap of more than 4 inches (102 mm). Stripes on handrails shall comply with Figure S101.1(4) of Appendix S.
- 1. Demarcation lines shall not extend in front of exit doors that lead out of an exit enclosure and through which occupants must travel to complete the exit path.
- 2. Demarcation lines shall be continuous but need not extend into an area such as a dead end or an obstruction that is selected not to be outlined because it is not part of the egress path.
- 1. Demarcation lines shall not extend in front of exit doors that lead out of an exit enclosure and through which occupants must travel to complete the exit path.
- 2. Perimeter demarcation lines are not required on the sides of steps.
- 3. Perimeter demarcation lines are not required where an area such as a dead end or an obstruction is selected not to be outlined because it is not part of the egress path, the demarcation lines shall not be required in such area provided that a demarcation line is continuous across the floor.
1024.2.4.3 Transition. Where a wall-mounted demarcation line transitions to a floor-mounted demarcation line, or vice versa, the wall-mounted demarcation line shall drop vertically to the floor to meet a complementary extension of the floor-mounted demarcation line, thus forming a continuous marking. Transitioning demarcation lines shall comply with Figure S101.1(7) of Appendix S.
1024.2.5 Obstacles. Obstacles at or below 6 feet 6 inches (1981 mm) in height and projecting more than 4 inches (102 mm) into the egress path shall be outlined with markings no less than 1 inch (25 mm) in width comprised of a pattern of alternating equal bands, of luminescent luminous material and black, with the alternating bands no more than 2 inches (51 mm) thick and angled at 45 degrees (0.79 rad). Obstacles shall include, but are not limited to, standpipes, hose cabinets, wall projections and restricted height areas. However, such markings shall not conceal any required information or indicators including, but not limited to, instructions to occupants for the use of standpipes. Markings on obstacles shall comply with Figure S101.1(6) of Appendix S.
1024.2.6 Doors from exit enclosures. Doors through which occupants within an exit enclosure must pass in order to complete the exit path, and doors serving horizontal exits, shall be provided with markings complying with Sections 1024.2.6.1 through 1024.2.6.3 of this chapter and Figures S101.1(11) and S101.1(12) of Appendix S. Exit discharge doors shall further comply with Section 1024.2.6.1.2.
1024.2.6.1 Emergency exit symbol. The doors shall be identified by a low-location luminous emergency exit symbol complying with Section 1024.6.1. The exit symbol shall be a minimum of 4 inches (102 mm) in height and shall be mounted on the door itself in accordance with Section 1024.2.6.1.1. Such signs shall be no higher than 18 inches (457 mm) above the finished floor.
1024.2.6.1.1 Mounting location. The vertical centerline of the sign shall be centered with the door, or shall be in that half of the door, either the right or left, that contains the latch. In case of double-doors, both doors shall be marked and the signs shall be centered with the doors. Arrows may be omitted on door-mounted signs. Door-mounted signs shall comply with Figure S101.1(1) in Appendix S.
1024.2.6.1.2 Exit discharge doors. At doors serving as exit discharge, a sign in compliance with Section 1024.2.6.1.1 shall contain supplemental directional text such as “FINAL EXIT,” “EXIT THROUGH LOBBY,” or “EXIT TO STREET” in sans serif letters one-half as high as the word EXIT. Exit discharge door sign shall comply with Figure S101.1(13) in Appendix S.
1024.2.6.2 Door hardware markings. Door hardware shall be marked with no less than 16 square inches (406 mm2) of luminous material. This marking shall be located behind, immediately adjacent to or on the door handle and/or escutcheon. Where a panic bar is installed, such material shall be no less than 1 inch (25 mm) wide for the entire length of the actuating bar or touchpad. Additional hardware markings may include ANSI Z 535.1 safety green graphics such as arrows indicating door handle turning directions, or emergency egress symbols as per NFPA 170, the word “EXIT,” the word “PUSH,” and similar egress-related symbols, provided the minimum 16 square inches (406 mm2) of luminous materials is maintained.
1024.2.6.3 Door frame markings. The top and sides of the door frame shall be marked with a solid and continuous 1 inch to 2 inch (25 mm to 51 mm) wide stripe. Where the door molding does not provide sufficient flat surface on which to locate the stripe, the stripe shall be permitted to be located on the wall surrounding the frame.
1024.2.7 Directional signage upon entering an exit enclosure. Luminous directional signs designed in compliance with Section 1024.6.1 shall be placed in the exit enclosure at every entrance thereto such that they are readily visible when the doors are in the open and closed positions. Such directional sign shall include an arrow indicating the direction of travel. The word “EXIT” shall not be required. The signs shall be located such that their top edge is within 18 inches (457 mm) above the finished floor. Directional signs shall comply with Figure S101.1(9) in Appendix S.
1024.2.8 Directional signage at transfer levels and where egress direction is not clear. Luminous directional signs designed in compliance with Section 1024.6.1 and installed at heights indicated in Section 1024.2.7 shall be placed on the wall at transfer levels and wherever egress direction is not clear; including at turns along horizontal extensions, at transitions from vertical to horizontal direction and at a “T” intersection. These directional signs shall include arrows indicating the direction of travel. The word “EXIT” shall not be required. Directional signs at transfer levels shall comply with Figure S101.1(9) in Appendix S.
1024.2.9 “No Exit” sign. Luminous signs shall be placed on doors along the egress path that lead to dead ends (mechanical rooms, storage closets, etc.). Such signs shall contain sans serif lettering at least 1 inch(25 mm) high reading “NO EXIT, “with the “NO” centered above the “EXIT. “The “NO” may be a larger size than the “EXIT” for clarity. The nonluminous portion of such signs shall not be green. No-exit signs shall comply with Figure S101.1(10) in Appendix S.
1024.3 Uniformity. Placement and dimensions of markings shall be consistent and uniform throughout the same exit enclosure.
1024.3.1 Solid and continuous. For the purposes of this section, solid and continuous means without gaps or interruption, except as required for the control of expansion and contraction. A series of dashes, chevrons, dots, or other similar patterns is not solid and continuous. Luminous materials shall be considered solid and continuous if they occasionally contain the following safety green (ANSI Z 535.1) symbols or text:
- 1. The word “EXIT”; \
- 2. Egress symbol as per NFPA 170;
- 3. Direction arrows as per NFPA 170; or
- 4. Other text or symbols as approved by the commissioner.
- 1. UL 1994; or\
- 2. ASTM E 2072, except that the charging source shall be 1 foot-candle (11 lux) of fluorescent illumination for 60 minutes, and the minimum luminance shall be 30 millicandelas per square meter at 10 minutes and 5 millicandelas per square meter after 90 minutes.
1024.5 Reserved.
1024.6 General standards. Luminous materials shall comply with the design standards of Sections 1024.6.1 and 1024.6.2.
1024.6.1 Design of door and directional signs. Unless otherwise specified, all photoluminescent door signs and directional signs:
- 1. May be either positive or negative image;
- 2. Shall be made with the non-photoluminescent portions of the signs in safety green as per ANSI Z535.1; and
- 3. Shall include three components:
- 3.1. The word “EXIT” printed in sans serif letters at least 4 inches high (102 mm) with strokes no less than ½ inch(13 mm);
- 3.2. An emergency exit symbol at least 4 inches high (102 mm), complying with NFPA 170; and
- 3.3. An arrow at least 2¾ inches (70 mm) high, complying with NFPA 170.
1024.6.1.1 Additional text for sign subject to this section. Additional descriptive text is permitted, provided such words are in sans serif letters and, where the word “EXIT” or the emergency symbol is required on such sign, such a descriptive text is no more than one-half as high as the word “EXIT” or the emergency exit symbol.
1024.6.2 Figures. The figures in Appendix S are intended only for illustration, and where there is a conflict between the figures and this section, this section shall govern.
1024.7 Voluntary installation. Where luminous egress path markings are not required but are voluntarily installed in the exit path, such markings shall comply with Section 1024.
1024.8 Special inspection. Luminous exit path markings shall be subject to special inspection in accordance with Sections 1024.8.1 through 1024.8.3.
1024.8.1 Inspection. A registered design professional shall verify by visual inspection that all components have been installed in accordance with Section 1024, both with the normal lighting turned on and with the normal and emergency lighting turned off.
1024.8.2 Product identification. A registered design professional shall review the manufacturer product literature and information from the testing agency and verify that the products installed are labeled as meeting the standards in Section 1024.4. The registered design professional shall verify which particular products were installed in which parts of the building.
1024.8.3 Paints. Where in situ painting was utilized, a registered design professional shallfield-verify that the specified paint was utilized in accordance with the manufacturer recommended methods of application.
1024.9 Maintenance program. Owners shall keep the required luminous egress path markings in good repair. At a minimum, owners shall, every 12 months, perform a visual inspection of the markings with the normal lighting turned on. Markings that are missing, damaged, loose, or that show signs of wear or missing labels shall be noted and promptly repaired. The log of such inspections, including the results and any corrective measures taken, shall be kept and maintained on the premises for inspection by the department and the Fire Department. The log shall contain the date of inspection and the printed name and signature of the person performing the inspection.
APPENDIX S
SECTION BC S101 GENERAL
S101.1 Scope. The figures of this appendix shall supplement the provisions of luminous egress path markings in Section 1024 and are intended for illustrative purposes. Where there is a conflict between the figures and the provisions in Section 1024, the provisions in Section 1024 shall govern.

















